O PTIONAL P LUG - IN C ARDS
ADDING OPTION CARDS
The CUB5 meters can be fitted with optional output cards and/or serial
communications cards. The details for the plug-in cards can be reviewed in the
specification section below. The plug-in cards, that are sold separately, can be
installed initially or at a later date.
WARNING: Disconnect all power to the unit before installing
Plug-in card.
Note : Measurement errors may occur if signal input common is shared with
another circuit common (ie, serial common, Dual Sinking Output option card,
or Power Supply common) on multiple units.
SINGLE RELAY CARD
Type : Single FORM-C relay
Isolation To Sensor & User Input Commons : 1400 Vrms for 1 min.
Working Voltage: 150 Vrms
Contact Rating : 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive
Life Expectancy : 100,000 minimum operations
DUAL SINKING OUTPUT CARD
Type : Non-isolated switched DC, N Channel open drain MOSFET
Current Rating : 100 mA max.
V DS ON : 0.7 V @ 100 mA
V DS MAX : 30 VDC
Offstate Leakage Current : 0.5 mA max.
RS485 SERIAL COMMUNICATIONS CARD
Type : RS485 multi-point balanced interface (non-isolated)
Baud Rate : 300 to 38.4k
Data Format : 7/8 bits; odd, even, or no parity
Bus Address : 0 to 99; max 32 meters per line
Transmit Delay : Selectable (refer to CUB5COM bulletin)
RS232 SERIAL COMMUNICATIONS CARD
Type : RS232 half duplex (non-isolated)
Baud Rate : 300 to 38.4k
Data Format : 7/8 bits; odd, even, or no parity
USB PROGRAMMING CARD
Type : USB virtual comms port
Connection : Type B
Baud Rate : 300 to 38.4k
Unit Address : 0 to 99
1.0 I NSTALLING
THE
M ETER
BEZEL
MOUNTING SCREW
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed. The
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from
the unit. Slide the panel gasket over the rear of the
unit to the back of the bezel. The unit should be
installed fully assembled. Insert the unit into the
panel cutout.
NUT FASTENER
PANEL
While holding the unit in place, push the panel latch over the rear of the unit
so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten the latch screws evenly until the unit is snug in the panel (Torque to
approx. 28 to 36 in-oz [0.202 to 0.26 N-m]). Do not over-tighten the screws.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating
temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
2.68
(68 +.8 )
1.30
(33 +.6 )
PANEL
GASKET
MOUNTING CLIP
+.025
-.000
-.0
+.024
-.000
-.0
2.0 S ETTING
THE
J UMPERS
INPUT RANGE JUMPER
This jumper is used to select the proper input range. The input range selected
in programming must match the jumper setting. Select a range that is high
enough to accommodate the maximum input to avoid overloads. To access the
jumper, remove the rear cover of the meter.
INPUT RANGE JUMPER
Warning : Exposed line voltage exists on the circuit boards. Remove
all power to the meter and load circuits before accessing inside of
the meter.
REMOVING THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd
input terminals. To release the tab, insert a small, flat blade screwdriver between
the tab and the plastic wall below the terminals. Inserting the screwdriver will
provide enough pressure to release the tab locks. To replace the cover, align the
cover with the input terminals and press down until the cover snaps into place.
3
MAIN CIRCUIT
BOARD
INPUT RANGE
JUMPER LOCATION
相关PDF资料
CUR-3285-MB BOX ABS 8.25X5.15X3.13" BLACK
CUR-3286-MB BOX ABS 10.15X6.15X3.13" BLACK
CUR-793-MB BOX ABS 4.1" X 2.23" X 2" W/BKTS
CUSTOM BGA CUSTOM BGA SOCKETS
CW2500 EPOXY OVERCOAT 0.26OZ
CW7000 BA DISPENSING PENS 2 PER PACKAGE
CWI45-B-155.52M CRY 155.25M 50PPM TH
CWR06NC105MR CAP TANT 1UF 50V 20% 2010
相关代理商/技术参数
CUB70000 功能描述:COUNTER 8-DIGIT REFLECTIVE DISP RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB70010 功能描述:COUNTER 8-DIGIT YEL/GRN BACKLIT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB70020 功能描述:COUNTER 8-DIGIT RED BACKLIGHT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB7CCG0 功能描述:COUNTER 8-DIGIT LV GREEN RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB7CCR0 功能描述:COUNTER 8-DIGIT LV RED BACKLIGHT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB7CCS0 功能描述:COUNTER 8-DIGIT LV REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB7CVG0 功能描述:COUNTER 8-DIGIT HV GREEN RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB7CVR0 功能描述:COUNTER 8-DIGIT HV RED RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮